Control valves, actuators, ESD and SIL systems

Executive bodies of the technological process. We select according to the environment, pressure, temperature, and the required coefficient of throughput Kv. Regulating - for continuous flow control, cut-off - for closing and overlapping operations. Safety SPR - for critical tasks (explosive zones, boilers, reactors).

DN15-1000diameters
0-700 barpressure
SIL 2-3safety
Equipment-type illustration: Control valves, actuators, ESD and SIL systems

The executive mechanism (drive) is a unit that converts a 4-20 mA control signal or compressed air into mechanical movement of a valve stem or disc: electric, pneumatic or hydraulic. A control valve with an actuator and a positioner keeps the flow at a set level, the shut-off valve simply opens or closes the passage at the command of the emergency protection or operator.

Control valve with a pneumatic drive and a positioner on the process pipeline · photo: Sonny Vermeer / Pexels
Types & Configurations

Types & Configurations

Each type is a separate range of parameters and its own task. A wrong choice here leads to overspending or downtime.

Control valvesThrough with a regulating cone, corner, bridge. For continuous adjustment of technological parameters.Analogues: SAMSON · Fisher · Spirax Sarco · Flowserve
Shut-off valvesBall, disk, layer. To quickly disconnect the flow in case of an accident or change of mode.Analogues: VanLift · Tyco · Camflex · Velan
Safety SDRs SIL 2-3Systems of fire protection, emergency shutdown of oil and gas and chemistry. Double reservation.Analogues: SAMSON · Fisher · Emerson · METRIC Group
Electric drivesMulti-rotating and rotary, with modular control, remote positioning. For shut-off and control valves.Analogues: AUMA · Rotork · Bernard · Limitorque
Pneumatic drivesPiston and membrane, fast in response, safe in Ex zones. Standard for responsible compartments.Analogues: SAMSON · Festo · ARI-Armaturen · El-O-Matic
What to Ask in RFQ

Parameters Without Which Selection Does Not Start

Type and constructionPass-through, angular, spherical, disk, rotary. Depends on the process and environment.
Nominal diameter DNFrom 15 mm to 1000 mm. It is selected according to the volume of the flow and the required Kv.
Pressure and temperatureWorking and test pressure, temperature range. Standard PN16/PN40/PN64.
MaterialCast iron, steel, stainless steel 304/316, duplex for aggressive environments.
SIL certificationSIL 1 - conventional systems, SIL 2-3 - critical, with redundancy and self-testing.
Where Delivery Works

Typical Applications

Regulation of pressure in the pipelineControl valve DN50-DN300 with pneumatic drive and 4-20 mA positioner.
Emergency shutdownShut-off ball valve DN200 with pneumatic drive and limit switches.
Reactor safety systemSIL 3 with dual drive redundancy and four feedback switches.
Dosage of reagentsSmall control valve DN15-DN50 with electric drive for accurate dosing.
Market Overview

What is Actually Ordered in Ukraine

The premium segment of valves and actuators is held by European SAMSON (Germany), Auma, Rotork (Great Britain), American Fisher (Emerson). Their products are a standard for oil and gas, chemistry, energy, and pharmaceuticals. Korean Flowserve - strong in oil refining. Spirax Sarco - the standard for steam systems. Bernard - in the French energy market. For typical industrial tasks (water, air, lubricant, low pressure) - Italian and Polish manufacturers provide 80% of the market at a 30-50% lower price. For SIL systems and responsible objects - only originals with a full certification package.

Kvs, shutter characteristic, travel time, failsafe position

Four specification parameters that determine whether a valve will fit a specific process circuit, not just a pipe diameter.

ParameterWhat does meanPractical significance
KvsThroughput when the gate is fully open — water consumption in m³/h at a pressure drop of 1 barThe standard size of the valve is selected by Kvs, and not by the DN of the pipeline - valves of the same DN with different passage profiles give different Kvs
Characteristics of the shutterLinear - the consumption is directly proportional to the stroke of the rod; equal percentage - the expenditure grows exponentiallyLinear is chosen when there is a constant pressure drop across the valve, equal percentage — when the drop changes with the load, i.e. in most real circuits
Running timeThe time it takes for the rod or disk to move completely from the closed to the open positionPneumatic drive — 2-10 seconds, electric drive — 15-60 seconds, hydraulic drive gives comparable speed even on large DN due to high pressure of working fluid
DisclaimerWhere does the valve go when the signal or power is lost: FC (fail close), FO (fail open), FL (fail last — remains in place)FO is typical for emergency steam release, FC is for fuel or reagent supply. The technology dictates the choice, not the vendor's habit

Electric, pneumatic or hydraulic: what are the criteria for choosing a drive

The type of energy that drives the stem determines not only the price, but also what will happen to the valve in a facility accident.

The presence of compressed air on the site

The pneumatic drive is the cheapest and fastest, but without a compressor station and a diluted 6-8 bar line, it makes no sense to install it - then it is cheaper to install an electric drive right away.

The required torque on large DNs

For valves and ball valves from DN300 and above, the electric drive is cumbersome and slow. Hydraulics on the same diameter gives a much higher moment with more compact dimensions - that's why it dominates dams, locks, and large shut-off valves for oil and gas.

Reaction speed for emergency protection

If the valve needs to close in seconds in case of gas or fire, a spring-return pneumatic actuator is practically the only option. At such a speed, the electric drive cannot withstand the mechanics for a long time.

Positioning accuracy in the control loop

An electric drive with a digital positioner keeps the set position of the rod more stable than a pneumatic drive without feedback — where precision is important, not speed, electricity wins.

Infrastructure cost versus drive cost

The hydraulic drive itself is more expensive than an electric or pneumatic drive of comparable torque, and an oil station with a pump and accumulator is additionally required — justified only where the torque or speed is critical, and not for economy.

Positioners: why does the valve need another device besides the drive

The actuator moves the rod, the positioner makes sure the rod stops exactly where the controller says, not where friction and pressure drop will allow.

Analog positioner

Receives a 4-20 mA signal, compares it with the actual position of the rod with a mechanical cam and supplies air to the drive until the position coincides with the specified one. Simple, reliable, without diagnostics.

Digital HART positioner

The same principle plus self-diagnosis of the drive, automatic calibration of the stroke at start-up and the ability to start a partial stroke (partial stroke test) directly from the control room — this is the check of the valve's serviceability in SIL systems without stopping the process.

When the positioner is mandatory

On any control valve - without it, the control circuit does not keep the set flow accurately. A positioner is usually not needed on a shut-off valve: there are enough "open/closed" limit switches.

What is a logic valve and why pneumology is needed

A term from a different category of equipment than the control and shut-off valves above, but is often searched for on the same catalog page.

A logic valve (logic element) is not a shut-off or control valve on a pipeline, but a component of a pneumatic control circuit that performs an AND or OR logic function with compressed air itself, without any electronics. Element I transmits a signal to the output only when there is simultaneous pressure on both inputs — it is used where the action can be performed only if two conditions coincide, for example, pressing two emergency start buttons at the same time. The OR element passes the signal if there is pressure on at least one of the inputs - a typical application: two independent sources of the "stop" command, each of which must independently stop the system.

In practice, logic valves are assembled in pneumatic panels for emergency protection (ESD) in wells, compressor stations and in explosive areas, where electronic protection is either duplicated or avoided altogether due to more complex expertise and requirements for explosion protection of electronics. The purely pneumatic logic does not depend on the power supply and remains operational even when the object is completely de-energized - this is the reason why this class of equipment is still included in new projects next to modern SIL-systems, and not completely replaced by them.

Ball (layer) valves and rotary valves - where each is justified

Two of the most common designs of shut-off valves, which are often confused with each other due to a similar field of application.

Ball (layer) valve

The hole in the ball opens the passage completely - minimal hydraulic resistance, a quarter turn to close. Standard for small and medium DN shut-off valves where full opening without throttling is required.

Disc rotary shutter (butterfly)

The disc rotates across the flow, lighter and cheaper than a ball valve on large DNs from 200 mm and above, but creates more hydraulic resistance even in the open position.

Choose by diameter, not by habit

At DN15-150, a ball valve is usually cheaper and more reliable, at DN300 and above, a disc valve wins in terms of weight and price — the crossover point lies somewhere between DN150 and DN250, depending on the pressure and the manufacturer.

Frequently Asked Questions

FAQ

Electric or pneumatic drive?

Electro - more accurate, smoother, without external power. Pneumo - faster, safer in Ex-zones, simpler. For regulating ones, pneumatics with a positioner are more common, for cut-off ones - it depends on the place.

What does SIL 2 mean?

Probability of failure on demand 10⁻³-10⁻², that is, 1 false alarm per 100-1000 requests. It is enough for ordinary security systems. SIL 3 - for critical (nuclear, oil and gas).

How much is the SAMSON valve DN50?

Include the model or specifications, quantity and delivery location. We will confirm price, availability and lead time in our reply.

Do you retrofit existing valves?

Yes. Replacing drives with modern ones with 4-20 mA control, adding positioners for adjustment, updating position indicators and limit switches.

What is a logic valve?

A logic valve (logic element) is a component of a pneumatic control circuit that performs an AND or OR function with compressed air itself, without electronics. The AND element transmits a signal only when both inputs are pressed simultaneously, the OR element — when at least one is pressed. Used in pneumatic panels of emergency protection, where electronics are avoided or duplicated.

How does the actuator differ from the valve drive?

In industrial terminology, these are synonyms: executive mechanism is the general name of a node that converts a control signal into mechanical movement, drive is the same concept closer to colloquial engineering language. There are executive mechanisms not only for valves, but also for dampers, shutters or ventilation dampers - the principle of operation is the same.

What are industrial executive mechanisms?

According to the type of energy — electric, pneumatic and hydraulic. Electric ones are more accurate and do not require compressed air, pneumatic ones are the fastest and safest in explosive areas, hydraulic ones develop the greatest torque on large diameters — dam valves, sluice gates, large oil and gas shut-off valves. The choice is determined by the facility's available infrastructure and speed requirements.

What is the Kvs of a valve?

Kvs is the throughput of the valve with the valve fully open: water flow in cubic meters per hour at a pressure drop of 1 bar across the valve. The standard size is selected precisely according to Kvs, and not according to the diameter of the pipeline - two valves of the same DN can have different Kvs depending on the profile of the passage.

Linear or equal percentage characteristic of the shutter - which one to choose?

Linear is chosen when the pressure drop across the valve remains practically constant — the flow is then directly proportional to the stroke of the stem. Equal-percent, where the flow rate grows exponentially, is taken when the pressure drop changes along with the system load — this is the majority of real technological circuits, so in practice, equal-percent happens more often.

What does the FC and FO fail-safe clause mean?

FC (fail close) means that the valve closes when the control signal or power is lost, FO (fail open) means that it opens. The choice is determined by the technology: FO is typically used to relieve excess steam pressure, FC is used to supply fuel or a dangerous reagent. There is also FL (fail last), when the valve simply remains in the last position.

Why a valve positioner, if there is already a drive?

The actuator only moves the rod, and the positioner verifies the actual position with a 4-20 mA control signal and compensates for friction, wear, and differential pressure that would otherwise displace the rod from the set point. Without a positioner, the control valve does not keep the exact flow, it is usually not put on the cut-off - there are enough limit switches.

When does a valve need a hydraulic drive instead of an electric drive?

When a large torque is required on diameters from DN300 and above, an electric drive of comparable power is bulky and slow, and hydraulics on the same dimensions develop a torque many times greater. Typical objects are gate valves of dams and sluices, large shut-off valves for oil and gas, where the compactness of the drive is more important than the cost of the oil station.