Instrumentation sensors: pressure, level, flow, analysis
Eyes and ears of industrial automation. We select sensors by parameter (pressure, temperature, level, consumption, analysis), environment (aggressive, food, oil and gas), measurement range, accuracy, certification for explosive zones. Standard 4-20 mA signal or digital HART, ProfiBus PA for responsible facilities.

KVPiA — control and measuring devices and automation: sensors, transmitters and regulators that measure a technological parameter and transmit a signal to the control system. The transducer (sensor) converts pressure, temperature, level or flow into an electrical signal, the transmitter amplifies and standardizes it to 4-20 mA, HART or Modbus for transmission to a PLC or SCADA.
Types & Configurations
Each type is a separate range of parameters and its own task. A wrong choice here leads to overspending or downtime.
Parameters Without Which Selection Does Not Start
| Measuring range | It is selected with a 2-3× margin to the peak values of the process. |
| Accuracy | ±0.1% for responsible, ±0.5-1% for technological, ±2% for indicator. |
| Signal | 4-20 mA analog, HART (4-20 with digital overlay), ProfiBus PA, Foundation Fieldbus. |
| Protection | IP65 for cabinets, IP66/IP67 for field, IP68 for immersion. |
| Explosion protection | ATEX Ex i (intrinsically safe), Ex d (explosion-proof) for oil and gas and chemicals. |
Typical Applications
What is Actually Ordered in Ukraine
KVPiA, transmitter, transmitter, transducer - where is the limit
Abbreviation and three terms that are used almost as synonyms in the specifications and tender documents, although they mean different nodes of the measuring circuit.
KVPiA is not the name of a specific device, but a whole class of equipment: pressure, temperature, level and flow sensors, regulators, executive mechanisms and controllers, which together form a process measurement and control circuit. In specifications and government procurement, the abbreviation is often simply in the name of the item — "pressure sensor (KVPiA)" — in order to assign the product to the correct product group according to UKTZED.
Transducer (in Ukrainian-speaking DSTUs this term is used, "sensor" is a fixed trace from Russian) perceives a physical quantity and converts it into a primary signal: a change in resistance, capacity, or frequency. The transmitter takes this weak and non-standard signal, amplifies and linearizes it to industrial form - 4-20mA, HART overlay to analog current or digital Modbus RTU. Transducer is a broader term in English-language documentation that covers both transducer and transmitter together.
For the customer, the difference is significant in one place — in the text of the technical specifications. If simply "pressure sensor" is specified, the supplier will default to a compact transmitter with a sensitive element inside a single housing - this is how most modern devices are arranged. A separate transmitter without built-in electronics is ordered less often, mostly for special projects with its own signal processing board.
Transmission protocols: 4-20 mA, HART, Modbus, ProfiBus PA
The signal determines how much information from the sensor reaches the controller - just a number or also device diagnostics.
| Signal/protocol | Type | Range | Which gives more than measurement |
|---|---|---|---|
| 4-20 mA | Analog, point-to-point | up to 1.5-3 km without reinforcement | Only parameter values, no diagnostics |
| HART | Digital overlay for 4-20 mA | up to 3 km along the same pair | Remote configuration, self-diagnosis, second variable value |
| Modbus RTU (RS-485) | Digital, bus | up to 1200 m, up to 32 devices on the line | Several parameters from one device, less cable to the cabinet |
| ProfiBus PA / Foundation Fieldbus | Digital bus for Ex-zones | up to 1900 m with repeaters | Power supply and signal in one pair, safe in explosive zone |
What are the criteria for choosing a sensor under TK
The procedure in which the engineer usually checks the specification before agreeing with the supplier.
Range with margin
Take a 2-3x reserve to the peak value of the process, and not to the nominal value - short-term pressure emissions at the start of the pump will otherwise lead the sensor to the limit of the scale.
Material of wetted part
316L stainless steel for most liquids, Hastelloy or tantalum for acids and chlorides. An error here reduces the life of the device to several months.
Response time
For the control loop, a speed of hundreds of milliseconds is important, and a few seconds are enough to archive a parameter in SCADA — it makes no sense to overpay for a fast sensor where it is not needed.
Process connection thread or flange
G1/2, M20×1.5 or DN50 PN16 flange - if not specified in the technical specifications, the supplier will choose at his own discretion, and the connection may not fit the existing boss during installation.
Explosion protection class for the zone
Ex ia for zone 0 with constant gasification, Ex d for zone 1-2. An overcharged claim is an overpayment, an undercharged one is a refusal of an industrial safety examination.
Sensors and transmitters for power grid monitoring
A separate class of KVPiA is not for the technological process, but for the state of the enterprise's electrical network itself.
Measuring current transformers (CT)
Reduce the primary current of hundreds to thousands of amperes to the standard 5 A or 1 A on the secondary winding for meters and protections. Accuracy class 0.2S for commercial accounting, 0.5 for technological.
Voltage and current converters with an output of 4-20 mA
The readings are transmitted to the PLC or ASKOE where there is no direct digital channel from the meter.
Power quality analyzers
Record harmonics, dips and voltage asymmetry, number of switches. Standard for inputs from 0.4 kV on objects with frequency drives that themselves generate harmonics.
Multifunctional counters with Modbus
One device closes the accounting and monitoring: active and reactive power, cos φ — the data enters the same SCADA as the technological sensors. On the market there are lines such as Schneider PowerLogic, Siemens SENTRON, Carlo Gavazzi.
Connectors and cable entries for field devices
The detail of the order is no less important than the transmitter itself - without it, the device will arrive, and connecting it will be useless.
Connector M12 (4-pin)
Standard for most modern pressure and temperature transmitters. Quick installation without opening the case, the corresponding cable is ordered as a separate item - it is often forgotten to be included in the specification.
Cable entry M20×1.5
For devices with a terminal box, where the cable is wound directly. A separate gland is required for the cross-section of a specific cable and the degree of protection IP67-IP68.
Han connector (industrial rectangular)
For multi-wire connection of transmitters with additional signals — emergency relay, second analog value.
Direct terminal connection
The cheapest option, but when replacing the device without a suitable connector, the line is stopped longer - the wires are crimped and signed on the spot, instead of changing the plug in a minute.
FAQ
How to choose a pressure sensor for a hydraulic system?
We proceed from the working pressure (usually 0-250 bar), presence of pulsations, oil temperature. Strain gauge in a stainless case with a 4-20 mA signal - standard. Protection IP67 for outdoor installation.
Pt100 or thermocouple?
Pt100 is more accurate (±0.1°C vs. ±1-2°C), slower (5-15 sec). A thermocouple is faster and can withstand higher temperatures (up to 1800°C versus 600°C). Pt100 for process control, thermocouple - for furnaces.
What is a level gauge for an aggressive liquid?
Radar non-contact with PTFE antenna or ultrasonic non-contact with PTFE membrane. Does not come into contact with liquid, resource does not depend on aggressiveness.
How much does the E+H pressure sensor cost?
Include the model or specifications, quantity and delivery location. We will confirm price, availability and lead time in our reply.
What is KVPiA?
KVPiA — control and measuring devices and automation: a collective name for sensors, transmitters, regulators and executive mechanisms that measure a process parameter (pressure, temperature, level, flow) and transmit a signal to the control system. In specifications and tenders, the term refers to an item in a product group, rather than describing a specific appliance.
Are transducers and sensors the same thing?
Yes. Davach is a Ukrainian term from DSTU, sensor is a fixed tracing from Russian, both refer to the same device that converts a physical quantity into a signal. In specifications, catalogs and tender documents, the terms are used as synonyms, and in practice this does not create confusion.
How does a transducer differ from a transmitter?
Transducer is a broader term: any device that converts one physical quantity to another, in particular to an electrical signal. A transmitter is a specific type of transducer that further amplifies and standardizes a signal to a 4-20mA or digital protocol for long distance transmission. Vendors often use these words interchangeably in specifications.
What sensors are needed to monitor the power grid?
Current and voltage measuring transformers, power quality analyzers and multi-functional meters with Modbus output are used for network accounting and monitoring. Unlike technological pressure or temperature sensors, they measure not the process, but the state of the power grid itself — current, voltage, harmonics, power.
How does RS-485 Modbus differ from HART for transmitting sensor data?
HART is a digital overlay on top of a regular 4-20mA analog signal: the main value is still current, the diagnostics are over the top. Modbus RTU over RS-485 is a purely digital bus without an analog component, up to 32 devices on one pair of wires, therefore cheaper when connecting many points at once.
What connectors are used to connect industrial sensors?
The most common is the M12 4-pin connector for quick installation without opening the case. For devices with a terminal box, a cable entry M20×1.5 with a gland for a specific cable cross-section is used. Both options provide IP67-IP68, the type of connector must be indicated in the technical specifications as a separate item.
What is the accuracy class of the sensor and how does it affect the price?
Compare configurations by operating parameters, materials, compatibility and scope of supply. Establish purchase-price and operating-cost differences from quotations based on the same requirements.
Is it possible to replace the sensor of one manufacturer with an analogue of another without reworking the cabinet?
If the signal (4-20 mA or Modbus), range, process connection and connector type match - yes, the replacement is direct. In practice, it is the connector that most often fails: the sensor with M12 will not fit into the cable, diluted for direct terminal connection, you will have to either change the cable or install an adapter.